5.2.5.5 Telediagnostic
Menu: FIDOR/Diagnostic/Telediagnostic
This menu shows an internal diagnosis (for service purposes).
Temperature – Flame – Actual flame temperature
– Detector – Actual temperature of analysis chamber
– Line – Actual temperature of heated line
– Catalyst – Actual temperature of catalyst
– Pt100-4 – Not used
– pAA – Actual temperature of pA amplifier
– Electronics – Actual temperature of electronics board
Pressure – P1 – Actual pressure detector
– P2 – Actual sample gas inlet pressure
– P4 – Actual combustion air pressure
– P5 – Actual fuel gas pressure
– P3 – Actual control air pressure
– P3-P2 – Pressure difference P3-P2
Voltage – Suction – Actual suction voltage
– 3.3V – Actual value of 3.3 V voltage supply
– 5V – Actual value of 5 V voltage supply
– 24V – Actual value of 24 V voltage supply
Current – Ignition – Actual ignition current of glow filament in A
Power – pAA – Heating output of pA-amplifier
– Detector – Heating output of detector
– Line – Heating output of heated line
– Catalyst – Heating output of internal catalyst
– Electric – Power of electronics
– Total – Total power
– Maximum – Maximum allowed power
Menu item Significance
Maintenance
request
– Short form of message (for a detailed description, see menu further on).
Failures – Short form of message (for a detailed description, see menu further on).
Monitoring – Status tracking of start process.
Start state – State saved after power-On.
Maint.req. xx – Actual pending maintenance requests.
Failures xx – Actual pending causes for failure.
Language – Language of telediagnostic error messages (German or English).